Sensors & Detection
Vent-Tel
(Previously Known As Panel Flo-Tel™)
Non-invasive ATEX approved burst detection for Explosion Vents
Elfab is unique in supplying a detection system as standard with its explosion vents. Vent (Panel) Flo-Tel™ is a non-invasive fail safe detection system providing an excellent solution for identifying when an explosion panel has functioned under harsh operating conditions.
System Operation
Operating on a simple read switch and magnet technology, Vent (Panel) Flo-Tel™ is designed to offer a practical solution for explosion vent detection.
- ATEX approved to category II 1 GD EEx ia IIC EC-Type Examination Certificate ITS03 ATEX 11359, must be connected to an intrinsically safe circuit.
- Sensor is not in contact with the process.
- Non invasive design
- Supplied integral to the vent.
Vent (Panel) Flo-TelTM should be connected to an intrinsically safe supply that is compatible with values:
- Ui = 30v
- Ii = 100 mA
- Pi = 0.75 W
- Supplied with a 2m cable
- Maximum process temperature 200 °C
- Minimum process temperature -100 °C